Type: | High-voltage |
---|---|
Structure: | Double-column Disconnector |
Installation: | Outdoor High-voltage |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No | Item | parameter | |||
1 | Rated Voltage kV | 72.5 | 123 | 145 | |
2 | Rated Current A | 630, 1250 | |||
3 | Rated Short Time withstand current and time kA/s | 25-40/4 | |||
4 | Rated Peak withstand current kA | 63-100 | |||
5 | 1min power frequency withstand voltage (effective value) kV | To earth | 140 | 230 | 275 |
To phase | 140 | 230 | 275 | ||
6 | Lightning impulse withstand voltage v(peak value) kV | To earth | 325 | 550 | 650 |
To phase | 325 | 550 | 650 | ||
7 | Rated mechanical terminaload N | Level of lateral load | 750 | 1500 | 1500 |
Level of vertical load | 500 | 1000 | 1000 | ||
Vertical force | 750 | 1000 | 1000 | ||
8 | Max Man Operative Moment N. m | 200 | |||
9 | control voltage V | AC220 DC110 or220 | |||
10 | motor voltage V | AC220 or380 DC110 or220 |