Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Still deciding? Get samples of US$ 10/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | YH10W5-12/33 |
Rated voltage---------kV | 12 |
MOCV ----------------kV | 10.2 |
Nominal Current-------kV | 10 |
Residual voltage of steep impulse----at 5kA(kV) | 36 |
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) | 33 |
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) | 25.4 |
1mA D.C reference voltage (kV) | 17 |
Line discharge level | 1 |
2mS long duration impulse current A | 400 |
4/10µS High current impulse kA | 100 |
Lightning impulse withstand kV | 110 |
Power frequency voltage withstand(dry/wet)kV | 28 |
0.1S TOV--------------kV | 14.4 |
1S TOV----------------kV | 13.8 |
10S TOV---------------kV | 13.2 |
1200S TOV-------------kV | 12 |
Creepage distance ----mm | 434 |
Material employed in series non-linear resistor | Zinc Oxide |