1. Lightning Arrester Packing details
1) Size: 370mmX130mmX320mm with 3pieces per carton
2) Packing: Carton with polyfoam insert parts
3)Weight: 7kg/carton
4)Loading Port: Ningbo/ Shanghai(Or as customer requirement)
5)Loading Ability: 20'GP 2264sets / 40'GP 3652sets
2. Lightning Arrester Working condition
1)Environment temperature: -40--+40 degree
2)altitude: <1000m
3)48Hz<Rated frequency<62Hz
4)Power frequency voltage should not be more than continuous running voltag
5)Max wind speed should be less than 35m/s
6)Earthquake intensity should be less than 7 degree
7)If used in contamination area, should be noted in advance.
3. Lightning Arrester Other information
About us:
Our company is founded in 1993year, with advanced technology and talents. To provide customers with the most satisfactory product quality and thoughtful service. We hope to develop together with you hand in
Hand, and make both of us win-win. I hope the majority of buyers can come visit and tour company,
Your satisfaction is our greatest pursuit.
Production Lead Time & Quality Guarantee:
Sample deliery time is about 2-3days
Big order quantity is about 30-35 days after we receive 30%~50% deposit from you.
Generally, it takes 4 working days by DHL/UPS, and 7-10days by EMS
12months' warranty period. 20years' quality guarantee period
With ISO9001: 2008approvals.
Customer Services:
Our salesmen will reply your inquiry within 24 hours. Any order is welcome. If you like to be our agent in your country, we can give you any support on the technique & other aspects.
Type |
YH5W5-30/80 |
|
|
Rated voltage---------kV |
30 |
4/10µS High current impulse kA |
65 |
MOCV ----------------kV |
24.4 |
Lightning impulse withstand kV |
150 |
Nominal Current-------kV |
5 |
Power frequency voltage withstand(dry/wet)kV |
70 |
Residual voltage of steep impulse----at 5kA(kV) |
86.5 |
0.1S TOV--------------kV |
36 |
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) |
80 |
1S TOV----------------kV |
34.5 |
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) |
/ |
10S TOV---------------kV |
33 |
1mA D.C reference voltage (kV) |
42.5 |
1200S TOV-------------kV |
30 |
Line discharge level |
1 |
Creepage distance ----mm |
1082 |
2mS long duration impulse current A |
250 |
Material employed in series non-linear resistor |
Zinc Oxide |