Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Still deciding? Get samples of US$ 10/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | Maximum System Voltage(kV) | Rated Voltage(kV) | Continuous Operating Voltage(kV) | MRV under 1/5 μ s Steep Discharge Current(kV) | MRV under 8/20 μ s Lightning Discharge Current(kV) | MRV under 30/60 μ s Operating Discharge Current (kV) | Line discharge class | Long duration impulse current at 2mS(A) | 4/10 μ s High Current Impulse(kA) | Outside insulation standard(at IEC or ANSI) (kV) | |||||||
IEC | ANSI | 5kA | 10kA | 5kA | 10kA | 0.5kA | 1kA | 2kA | Lightning impulse withstand voltage kV | Power frequency withstand voltage (kV) | |||||||
Y5W, Y10W-39 | 52 |
48.3 |
39 | 31.2 | 108 | 119 | 100 | 109 | / | / | / | 1 | 300 | 65 | 250 | 95 | 120/100 |
106 | 115 | 98 | 105 | 80.5 | 83 | 86.3 | 1 | 400 | 100 | ||||||||
Y5W, Y10W-42 | 42 | 33.6 | 118 | 129.5 | 109 | 119 | / | / | / | 1 | 300 | 65 | 250 | 95 | 120/100 | ||
114.5 | 124 | 106 | 114 | 87 | 90 | 93.3 | 1 | 400 | 100 | ||||||||
Y5W, Y10W-45 | 45 | 36 | 126 | 138 | 116 | 126.5 | / | / | / | 1 | 300 | 65 | 250 | 95 | 120/100 | ||
123.5 | 133 | 113 | 122 | 92.6 | 95.6 | 99.5 | 1 | 400 | 100 | ||||||||
Y5W, Y10W-48 | 48 | 38.4 | 131 | 141 | 120 | 129.5 | / | / | / | 1 | 400 | 100 | 250 | 95 | 120/100 | ||
125.6 | 138.8 | 115.3 | 127.3 | 98.5 | 102 | 106 | 2 | 600 | 100 | ||||||||
Y5W, Y10W-51 | 51 | 40.8 | 139.5 | 151.5 | 128 | 139 | / | / | / | 1 | 400 | 100 | 250 | 95 | 120/100 | ||
136 | 149 | 125 | 136.7 | 107 | 111 | 115 | 2 | 600 | 100 |