GW38-40.5~252/630~4000 Type Three post Horizontal Double break disconnector
Double break is good for reducing the distance and station arranging, especially for indoor station
Because of electric rod's self-rotation and switching structure and having self-locking function, it has strong property of motor performance resistance. Meanwhile, it can resist motor, wind pressure, earthquake and other outside power
Contact and finger's on and off way is sliding rotation, having strong self-clean ability.
In the galvanic circle, the section is the combination structure made by screw fix linking, having the good property of stable flowing, high reliability, simple change way and convenient adding volume way.
In the galvanic circle, the contact and finger is made by T2Y pure copper tap whose connecting part is coated by 30μ M silver.
Finger spring is made by the stainless steel and its design is the inside hiding and outside press structure which is convenient for testing and changing
The bearing has changed from the bevel rear structure to the Universal connecting rod drive structure, having the advantage of simple structure, high intensity, convenient operation way and safety enough.
Bearing block is made by high-intensity casting steel (disposed by hot zinc coating), the height can be adjusted and have the function of damping.
Have different install way such as front install, side install, back install and leak 25° Install and so on, adapting to different station entering line ways.
All the operating rod and linking rod are supplied by manufacturer, which is convenient for loading, adjusting and testing.
It can be supplied as a whole above the ground according to user's requirement.
No |
Item |
Technical parameter |
1 |
Rated Voltage kV |
72.5 |
123 |
145 |
245 |
2 |
Rated Current A |
1250 1600 2000 2500 3150 4000 |
3 |
Rated Short Time withstand current and Time kA/s |
25~50/4 |
4 |
Rated Peak withstand current kA |
63~125 |
5 |
1min power frequency withstand voltage (effective value) kV |
To earth |
140 |
230 |
275 |
460 |
To phase |
140 |
230 |
275 |
460 |
Across Isolating DS |
180 |
300 |
315 |
605 |
6 |
Lightning Impulse wishstand voltage
(peak value) kV |
To earth |
325 |
550 |
650 |
1050 |
To phase |
325 |
550 |
650 |
1050 |
Across Isolating DS |
405 |
650 |
750 |
1200 |
7 |
Rated mechanical terminal load N |
Level of lateral load |
750 |
1500 |
1500 |
2000 |
Level of vertical load |
500 |
1000 |
1000 |
1500 |
Vertical |
750 |
1000 |
1000 |
1250 |
8 |
Capacity and Inductive Ability (open and close) |
Capacity Current A |
1 |
Inductive Current A |
0.5 |
9 |
Max Man Operative Moment N. m |
200 |
10 |
Motor Drive operating mechanism control voltage V |
AC220; DC110, 220 |
11 |
Motor Drive operating mechanism motor voltage V |
AC220, 380; DC110, 220 |