Type: | Metal Oxide Surge Arrester |
---|---|
Structure: | Zinc Oxide Arrester |
Installation: | Parallel Arrester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical Parameters:
Type | YH10W5-15/41.2 | 4/10µS High current impulse kA | 100 |
Rated voltage---------kV | 15 | Lightning impulse withstand kV | 110 |
MCOV ----------------kV | 12.7 | Power frequency voltage withstand(dry/wet)kV | 28 |
Nominal Current-------kA | 10 | 0.1S TOV--------------kV | 18 |
Residual voltage of steep impulse----at 5kA(kV) | 44.5 | 1S TOV----------------kV | 17.25 |
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) | 41.2 | 10S TOV---------------kV | 16.5 |
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) | 31.5 | 1200S TOV-------------kV | 15 |
1mA D.C reference voltage (kV) | 21.2 | Creepage distance ----mm | 500 |
Line discharge level | 1 | Material employed in series non-linear resistor | Zinc Oxide |
2mS long duration impulse current A | 400 | Material of housing | silicone rubber |
Working condition:
Environment temperature: -40--+40 degree | |||||||
altitude:<1000m | |||||||
48HZ<Rated frequency<62HZ | |||||||
Power frequency voltage should not be more than continuous running voltage | |||||||
Max wind speed should be less than 35m/s | |||||||
Earthquake intensity should be less than 7 degree | |||||||
If used in contamination area, should be noted in advance. |