Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | Y10W5-132/344 |
Rated voltage---------kV | 132 |
MCOV ----------------kV | 106 |
Nominal Current-------kV | 10 |
Residual voltage of steep impulse----at 5kA(kV) | 396 |
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) | 334 |
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) | 263 |
1mA D.C reference voltage (kV) | 192 |
Line discharge level | 3 |
2mS long duration impulse current A | 850 |
4/10µS High current impulse kA | 100 |
Lightning impulse withstand kV | 650 |
Power frequency voltage withstand(dry/wet)kV | 275 |
0.1S TOV--------------kV | 158.4 |
1S TOV----------------kV | 151.8 |
10S TOV---------------kV | 145.2 |
1200S TOV-------------kV | 132 |
Creepage distance ----mm | 4250 |
Material employed in series non-linear resistor | Zinc Oxide |