Application: | High-voltage |
---|---|
Material: | Porcelain |
Structure: | Post Insulator |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Parameter Table | |||||
No | Items | Technical parameter | |||
1 | Rated Voltage kV | 72.5 | 126 | ||
2 | Nominal system voltage kV | 66 | 110 | ||
3 | Rated current A | 630;1250;1600;2000;2500;3150;4000 | |||
4 | Rated Short Time withstand current and Time kA/s | 25~50/4 | |||
5 | Rated Peak withstand current kA | 63~125 | |||
6 | 1min power frequency withstand voltage (effective value) kV | To earth | 140 | 230 | |
To phase | 140 | 2300 | |||
Across Isolating DS | 180 | 230+70 | |||
7 | Lightning Impulse wishstand voltage(peak value) KV | To earth | 325 | 550 | |
To phase | 325 | 500 | |||
Across Isolating DS | 385 | 550+100 | |||
8 | Rated mechanical terminal load N | Level of lateral load | 750 | 1500 | |
Level of vertical load | 500 | 1000 | |||
Vertical | 750 | 1000 | |||
9 | The min distance of insulation against ground mm | 600 | 1000 | ||
10 | Max Man Operative Moment N. m | 200 | |||
11 | Motor Drive operating mechanism control voltage V | AC220,380; DC110,220 | |||
12 | Motor Drive operating mechanism motor voltage V | AC220,380; DC110,220 |