| Type | YH10W5-24/66 |
| Rated voltage---------kV | 24 |
| MOCV ----------------kV | 19.5 |
| Nominal Current-------kV | 10 |
| Residual voltage of steep impulse----at 5kA(kV) | 71.5 |
| 8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) | 66 |
| Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) | 50 |
| 1mA D.C reference voltage (kV) | 34 |
| Line discharge level | 1 |
| 2mS long duration impulse current A | 400 |
| 4/10µS High current impulse kA | 100 |
| Lightning impulse withstand kV | 150 |
| Power frequency voltage withstand(dry/wet)kV | 50 |
| 0.1S TOV--------------kV | 28.8 |
| 1S TOV----------------kV | 27.6 |
| 10S TOV---------------kV | 26.4 |
| 1200S TOV-------------kV | 24 |
| Creepage distance ----mm | 824 |
| Material employed in series non-linear resistor | Zinc Oxide |